High frequency On Line ( LCD )
• 1KVA ~ 10KVA ( IP/OP:220Vac/230Vac/240Vac )
 

KEY FEATURESHigh frequency On Line ( LCD )

 Microprocessor Control Guarantees High Reliability
 Comprehensive Self-Protection Design
 Audible Alarm Mute
 Cold Start Function
 Auto Self-Testing System while Turning On UPS
 Wide Input Voltage Range
 Maintenance Bypass Switch for 6K/ 10K
 N+X Parallel Redundancy and Capacity Expansion for 6K/ 10K



TECHNICAL SPECIFICATIONS

 

MODEL

 

G1KD

G1KDS

G2KD

G2KDS

G3KD

G3KDS

G6KND

G6KNDS

G10KND

G10KNDS

CAPACITY

VA/W

1000VA/700W

2000VA/1400W

3000VA/2100W

6000VA/4200W

10000VA/7000W

INPUT

Phase

Single Phase with Ground

Frequency Range

50Hz:46~54Hz

Power Factor

>=0.97

>=0.98

Voltage Range

Base on load percentage (100%-80% / 80%-70% / 70%-60% / 60%-0%)

Line Low Transfer

160VAC/140VAC/120VAC/110VAC± 5VAC

176 ±3% VAC

Line Low Comeback

175VAC ± 5VAC

185 ± 3% VAC

Line High Transfer

300VAC± 5VAC

276 ± 3% VAC

Line High Comeback

285VAC± 5VAC

266 ± 3% VAC

OUTPUT

Phase

Single

Voltage

220VAC/230VAC/240VAC

Voltage Regulation

± 2%

± 1%

Frequency
( Synchronized Range)

46~54Hz

Frequency
( Battery Mode)

50 ± 0.2 Hz

50Hz ± 0.05Hz

Current Crest Ratio

3:1

Harmonic Distortion

?3% THD
( Linear Load)
?6% THD
( Non-Linear Load)

<4% THD ( Linear Load)
<7% THD ( Non-Linear Load)

?2% THD (Linear Load)
?6% THD (Non-Linear Load)

Output Waveform

Pure Sinewave

EFFICIENCY

To AC Mode

85%

85%

85%

> 88%

To Battery Mode

83%

83%

83%

> 88%

BATTERY

Battery Type

12V/7.2Ah

Depending on the capacity of external batteries

12V/7.2Ah

Depending on the capacity of external batteries

12V/7.2Ah

Depending on the capacity of external batteries

12V/7.2AH

Depending on the capacity of external batteries

12V/9Ah

Depending on the capacity of external batteries

Numbers of Batteries

3

8

8

20

20

Backup Time
(Full Load)

>5 minutes

>9 minutes

>5 minutes

8 minutes

5 minutes

Recharge Time

5 hours to 90%

5 hours to 90%

5 hours to 90%

7 hours to 90%

8 hours to 90%

Charging Current (Max.)

1.0A

7A

1.0A

8A+/-1A

1.0A

8A+/-1A

2.0A

4.2A

2.0A

4.2A

Charging Voltage

41.1Vdc ± 0.6V

110Vdc ± 0.4V

274Vdc ± 1%V

External Battery type

N/A

12V/7.2AH *3

N/A

12V/7.2AH *8

N/A

12V/7.2AH *8

N/A

12V/7.2AH *20

N/A

12V/9AH *20

TRANSFER TIME

AC to DC

Zero

Inverter to Bypass

2.5ms (Typical )

Zero

Operation interface

LED Indicator

Normal (green),warning(yellow),Fault(red)

LCD Indicator

Status,Voltage,Frequency,Battery Status,Temperature,History Record,Voltage set

AUDIBLE ALARM

Battery Mode

Sounding every 4 seconds

Low Battery

Sounding every second

Overload

Sounding twice every second

Fault

Continuously Sounding

DIMENSION

UPS Case D x W x H (mm)

400x145x220

460x192x340

570x260x717

Battery Case D x W x H

N/A

400*145*220

N/A

460*192*340

N/A

460*192*340

570*260*717

WEIGHT

Net Weight(kgs)

14

7

34.5

15

35.5

16

84

35

93

38

ENVIRO
NMENT

Operating Environment

0~40 Degrees Centigrade, 20~90% relative humidity (non-condensing)

Noise Level

<45dB @ 1 Meter

50dB @ 1 Meter

<55dB @ 1 meter

<55dB @ 1 meter

INTERFACE

Smart RS-232

Windows 98/NT/2000/XP/2003, Linux, Sun Solaris, IBM Aix, Compaq True64, SGI IRIX, FreeBSD, HP-UX, and MAC

SNMP (option)

Power management from SNMP manager and web browser



 
Please consult the factory or the distributors for further information of "S" models.

 Specifications are subject to change without notice