China Zhejiang Ward Electronic Co., Ltd.

 

High Frequency On Line UPS

--
UPS 1KVA ~ 3KVA
--
UPS 6KVA ~ 10KVA
--
UPS 10KVA ~ 20KVA
--
LCD UPS 1KVA ~ 10KVA
--
LCD UPS 10KVA ~ 20KVA
--
UPS 20KVA ~ 80KVA

Rack Mount On Line UPS

--
UPS 1KVA-6KVA
--
LCD RM UPS 110V
--
LCD RM UPS 220V

 Line Interactive UPS

--
Line Interactive UPS
--
Blazer (Modified Sine Wave Output Waveform)

Low Frequency On Line UPS

--
UPS 8KVA ~ 30KVA (1Ph Out)
--
UPS 10KVA ~ 300KVA (3Ph out)

Electric On Line UPS

--

High Frequency UPS 1KVA ~ 10KVA

--

Low Frequency UPS 10KVA ~ 45KVA


ARRAY UPS

--

Array UPS 4KVA ~ 24KVA (1 Ph Out)

--

Array UPS 15KVA ~120KVA (3 Ph Out)


 EPS (Emergency Power System)

--
EPS 0.5KW ~ 200KW


ACCESSORY

--

SNMP CARD

--

BATTERY CABINET

tieds UPS, UPS battery backup

Following the popularity of computer networks and the continual upgrades of information processing technology, there is now virtually no limits for network information transmissions. Undoubtedly, the server is the soul of a computer network which processes numerous network data day in and day out and is naturally more demanding in terms of power requirements computers in general. Any increase of power network load, excessively low voltage, unstable frequency or even a sudden power-off can interrupt normal network operations!
In line with the power requirements for network system, WARD has developed a new generation of on-line intelligent UPS, tieds UPS, UPS battery backup---GOLD Series 1K, 2K, 3K UPS. Its uses the Motorola microprocessor with robust processing power which is capable of detecting and controlling quickly and accurately all movements of the UPS to ensure high product reliability. In addition to providing the network with power protection for virtually zero interruption, regulated voltage and regulated frequency, interference-resistant capability and filtering of noisy signals, under normal conditions, utility power obtains via AC-DC circuit the DC bus voltage which is then converted to 220V AC output via the inverter, so as to safeguard the data over the entire network. Therefore, the power used by the load is the purified sine wave power via regulated voltage and regulated frequency with noisy signals filtered. Furthermore, WARD GOLD Series 1K, 2K, 3K UPS, tieds UPS, UPS battery backup are connected through the RS232 communication port to WARD Power Management software for power detection and power monitoring, to integrate UPS and the network server into one entity with power status available at any time. Moreover, it achieves the intelligent functions such as timer-controlled self-inspection, automatic disk-saving, automatic timer-controlled power-on and power-off and record of power status etc., to achieve the zero distance of communication between the user and UPS. Whenever utility power supply is interrupted, the UPS, tieds UPS, UPS battery backup will inform the server immediately and gets ready for switching off the unit and saving automatically all data before performing the normal power-off instruction. Even in an unattended network environment, the UPS can still ensure data safety of the network system.

APPLICATION

Servers, Data-Center Critical network devices, Sensitive electronic equipment, Telecom...

KEY FEATURES

. True on-line double conversion technology with advanced microprocessor control
. Wide input voltage range
. Zero transfer time
. Protection against all type of power problems
. Self test while start of the UPS
. Site wiring fault warning
. On-battery power-on function
. Smart RS232 communication interface
. Intelligent slot available
. Sealed lead-acid, maintenance free battery

tieds UPS, UPS battery backup

TECHNICAL SPECIFICATIONS

Product Series

GOLD

Model

G1K

G2K

G3K

Rated Power

VA/W

1kVA / 0.7kW

2kVA / 1.4kW

3kVA / 2.1kW

Input

Nominal Voltage

220VAC

Voltage Range

115 ~ 300VAC

Frequency Range

46~54Hz(default), user adjustable within 40~60Hz

Power Factor

0.97

Connection

IEC320-10A inlet

IEC320-16A inlet

Output

Voltage

220VAC ± 2%

Frequency

46~54Hz or 50Hz ± 0.2Hz (Line mode)
50Hz
± 0.2Hz ( Battery mode)

Waveform

Sine Wave

Distortion

3%

4%

Overload Capability

108%~150% for 30 sec., ³150% for 300 ms

Current Crest Ratio

3:1

Connections

IEC320 * 4

IEC320 * 6

IEC320 * 3 and
Terminal Block

Battery

Type

Sealed, Maintenance free, Lead-Acid (Panasonic)

Quantity

3 pieces

8 pieces

Back-up Time (Full load)

5 min

9 min

5 min

Recharge Time

5 hrs to 90% of capacity after full load discharge

Bypass 

 

Automatic Transfer

on overload and UPS failure

Before UPS Power-on

Default “NO”, user adjustable to “YES”

Voltage Range

80~264VAC (Default), user adjustable within 80~286VAC

Transfer Time

0 ms; less than 4 ms from inverter to bypass and vice versa

LED Indicators

Status

Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault

Audible Alarm

Bypass, On battery mode, Battery low, Overload, Fault

Acoustic Noise

At 1 meter distance

45 dBA

50 dBA

Communications

DB-9 Port

RS-232 Serial Interface

Intelligent Slot

Options: WebPower, AS400 Card or WinPower CMC

Network Surge Protection

RJ45 I/O port available for network or Fax/Modem

Environmental

Operating Temperature

0 ~ 40°C

Operating Humidity

20 ~ 90% non-condensing

Weight

Net (Kg)

13

31.5

32

Dimensions

W x D x H (mm)

145 x 400 x 220

192 x 460 x 348

G1KS, G2KS & G3KS for longer Backup time with additional Battery Packs are available, please consult local distributors.