Low Frequency UPS 10KVA ~ 45KVA
power system, uninterruptible power system

WARD DT series low frequency on line UPS, power system, uninterruptible power system from 10KVA to 45KVA. It’s designed special for data management center, manufacture industry, petrify system, metallurgical industry, power system etc. It’s adopted twin changing online design, intelligent IGBT module, PWM pulse-width modulation and several CPU, power system, uninterruptible power system control technology. It’s the best protection equipment for various kinds of important equipments.

FEATURES

High Reliable
* Adopt twin change on line technology, sequester extraneous interference
* Favorable overload ability and protection
* Design with 100% unbalance protection
* 100% Non linear load ability
* IGBT, PWM inverter together with digital

logic power control technology
* Industrial grade UPS

Super Safety
* The output isolate transformer can avoid the destruction of abnormal signal & lightning stroke
* With static bypass, repair bypass, battery maintain bypass
* Cold start
power system, uninterruptible power system

Smart
* Different loading have different use way. Single UPS, 1+1 or N+1 etc.
* Modular design, easy to repair
* Intelligent management for battery pack

Economic
* The efficiency of complete system more than 90%, it will be up to 95% or more if ECO mode

Easy Operation
* LED/LCD display, it’s easy to operate

Intelligent

* It can remote management and TVSS through the offered RS232()RS422, optional SNMP Card, RJ45 etc. communicate port

Appliance

* Data management equipment and system
* Automatic control systems
* Hospital
* Mini office system
* Telecommunication systems
* Bank
power system, uninterruptible power system

Technical Parameter

Model

DT10K

DT15K

DT20K

DT30K

DT45K

Rated Capacity

10KVA

15KVA

20KVA

30KVA

45KVA

DC Input

Voltage(VDC)

220VDC

Current (A)

45A

68A

90A

136A

205A

Voltage Range

200 ~ 280VDC

AC Input

Voltage

380VAC  (Three Phases Four Wires)+ G

Voltage Range

380VAC ± 15%

Frequency

45 ~ 60Hz

Power Factor

0.8

Bypass Input

Voltage Range

220VAC ±15%

Current (A)

45A

68A

90A

138A

205A

AC Output

Voltage

220VAC

Frequency

50Hz± 0.1%

Rated Output Current

36A

54A

72A

109A

164A

Voltage Accuracy

220VAC ±3%

Frequency Accuracy

50Hz ± 0.05

Distortion (THD)

< 5% (linear load)

Dynamic

± 5% (from 0 to 100% load and from 100% load to 0)

Power Factor

0.8

Overload Ability

120% for10 seconds

Crest Factor

3:1

Inverter Efficiency

92 % (80% linear load )

Transfer Time

0 ms (from AC power to DC power each other), 4ms (from inverter to bypass each other)

Protection

Input Protection

Opposite connection of null and battle line, under voltage, over voltage

Output Protection

Overload, short circuit, over temperature

Ambient

Insulate Degree

1500VAC, 1 min (Input & Output)

Noise

£55dB

Temperature

­10 °C ~ +40 °C

Humidity

0 ~ 90% (no dewfall)

Elevation

<1000m

Size (mm)

800x600x2200

300

400

450

500

600

Specifications are subject to change without notice