| Following the popularity of computer networks and the
continual upgrades of information processing technology,
there is now virtually no limits for network information
transmissions. Undoubtedly, the server is the soul of a
computer network which processes numerous network data day
in and day out and is naturally more demanding in terms
of power requirements computers in general. Any increase
of power network load, excessively low voltage, unstable
frequency or even a sudden power-off can interrupt normal
network operations!
In line with the power requirements for network system,
WARD has developed a new generation of on-line intelligent
UPS, tieds UPS, UPS battery backup---GOLD Series 1K, 2K, 3K UPS. Its uses the Motorola
microprocessor with robust processing power which is capable
of detecting and controlling quickly and accurately all
movements of the UPS to ensure high product reliability.
In addition to providing the network with power protection
for virtually zero interruption, regulated voltage and regulated
frequency, interference-resistant capability and filtering
of noisy signals, under normal conditions, utility power
obtains via AC-DC circuit the DC bus voltage which is then
converted to 220V AC output via the inverter, so as to safeguard
the data over the entire network. Therefore, the power used
by the load is the purified sine wave power via regulated
voltage and regulated frequency with noisy signals filtered.
Furthermore, WARD GOLD Series 1K, 2K, 3K UPS, tieds UPS, UPS battery backup are connected
through the RS232 communication port to WARD Power Management
software for power detection and power monitoring, to integrate
UPS and the network server into one entity with power status
available at any time. Moreover, it achieves the intelligent
functions such as timer-controlled self-inspection, automatic
disk-saving, automatic timer-controlled power-on and power-off
and record of power status etc., to achieve the zero distance
of communication between the user and UPS. Whenever utility
power supply is interrupted, the UPS, tieds UPS, UPS battery backup will inform the server
immediately and gets ready for switching off the unit and
saving automatically all data before performing the normal
power-off instruction. Even in an unattended network environment,
the UPS can still ensure data safety of the network system.
APPLICATION
Servers, Data-Center Critical network devices, Sensitive
electronic equipment, Telecom...
KEY FEATURES
. True on-line double conversion technology with advanced
microprocessor control
. Wide input voltage range
. Zero transfer time
. Protection against all type of power problems
. Self test while start of the UPS
. Site wiring fault warning
. On-battery power-on function
. Smart RS232 communication interface
. Intelligent slot available
. Sealed lead-acid, maintenance free battery
tieds UPS, UPS battery backup
TECHNICAL SPECIFICATIONS |
|
Product
Series |
GOLD |
|
Model |
G1K |
G2K |
G3K |
|
Rated
Power |
VA/W |
1kVA
/ 0.7kW |
2kVA
/ 1.4kW |
3kVA
/ 2.1kW |
|
Input |
Nominal
Voltage |
220VAC |
|
Voltage
Range |
115
~ 300VAC |
|
Frequency
Range |
46~54Hz(default),
user adjustable within 40~60Hz |
|
Power
Factor |
0.97 |
|
Connection |
IEC320-10A
inlet |
IEC320-16A
inlet |
|
Output |
Voltage |
220VAC
±
2% |
|
Frequency |
46~54Hz
or 50Hz ±
0.2Hz (Line mode)
50Hz ±
0.2Hz ( Battery
mode) |
|
Waveform |
Sine
Wave |
|
Distortion |
3% |
4% |
|
Overload
Capability |
108%~150%
for 30 sec., ³150%
for 300 ms |
|
Current
Crest Ratio |
3:1 |
|
Connections |
IEC320
* 4 |
IEC320
* 6 |
IEC320
* 3 and
Terminal Block |
|
Battery |
Type |
Sealed,
Maintenance free, Lead-Acid (Panasonic) |
|
Quantity |
3
pieces |
8
pieces |
|
Back-up
Time (Full load) |
5
min |
9
min |
5
min |
|
Recharge
Time |
5
hrs to 90% of capacity after full load discharge |
|
Bypass
|
Automatic
Transfer |
on
overload and UPS failure |
|
Before
UPS Power-on |
Default
“NO”, user adjustable to “YES” |
|
Voltage
Range |
80~264VAC
(Default), user adjustable within 80~286VAC |
|
Transfer
Time |
0
ms; less than 4 ms from inverter to bypass and vice
versa |
|
LED
Indicators |
Status |
Load
level / Battery
level,
Battery
,
Utility Power, Inverter, Bypass, Overload, Fault |
|
Audible
Alarm |
Bypass,
On battery mode, Battery
low,
Overload, Fault |
|
Acoustic
Noise |
At
1 meter distance |
45
dBA |
50
dBA |
|
Communications |
DB-9
Port |
RS-232
Serial Interface |
|
Intelligent
Slot |
Options:
WebPower, AS400 Card or WinPower CMC |
|
Network
Surge Protection |
RJ45
I/O port available for network or Fax/Modem |
|
Environmental |
Operating
Temperature |
0
~ 40°C |
|
Operating
Humidity |
20
~ 90% non-condensing |
|
Weight |
Net
(Kg) |
13 |
31.5 |
32 |
|
Dimensions |
W
x D x H (mm) |
145
x 400 x 220 |
192
x 460 x 348 |
G1KS, G2KS & G3KS for longer Backup time with additional
Battery Packs are available, please consult local distributors.
|